Settings
LoginCompare (0)Jobs
Language:
English
  • fr Français
  • en English
LOAD PINS, TENSIOMETERS
LOAD CELLS, ELECTRONICS
Mon-Fri, 8am - 5.30pm (GMT+1)

Can I put 2 dynamometric axes on a load limiter ?

It is possible to connect 2 load-cells in parallel to a Bridge-Boy but in this case we cannot guarantee the positive safety.

The load limiter Bridge Boy has been designed for use with only ONE load cell in order to detect any problem on the load cell. For example, if a wire of only ONE load cell is cut, it is possible that the Bridge-Boy will not detect it.

For this reason is the CE certificate of compliance no longer valid in this case.

 

That is why we recommend the following schematics if you need to have a load limitation on the sum of the load of 2 load-cells.

CE certification is then available.